HOBO Plug Load Data Logger - UX120-018

Onset's HOBO Plug Load Data Logger is a high-accuracy, easy-to-deploy data logger that measures and records the power and energy consumption of 120V plug loads from office equipment, vending

  • Product Name:HOBO Plug Load Data Logger - UX120-018
  • Model: UX120-018
  • Maunufactor:Onset
  • Country:USA

Onset's HOBO Plug Load Data Logger is a high-accuracy, easy-to-deploy data logger that measures and records the power and energy consumption of 120V plug loads from office equipment, vending machines, and other devices.

Accurate and Rugged

The UL certified logger provides 0.5% measurement accuracy with a measurement resolution of 1 watt, making it an ideal choice for building audits where detailed energy use data is required. The rugged housing is designed to withstand the rigors of real-world handling, providing reliable performance despite bumps, drops, and use under desks.

Features:

  • 0.5% measurement accuracy enables more reliable plug load energy data

  • "Meter Mode" provides instant viewing of real-time plug load variables

  • Provides time-stamped and totalized load data for detailed energy analysis

  • Large memory enables faster logging intervals for more comprehensive plug load profiles

  • Battery back-up ensures logged data remains intact in the event of a power outage or load failure

  • Full-featured LCD display provides visual diagnostics for easy deployment

  • Compatible with HOBOware and HOBOware Pro software for logger setup, graphing and analysis


The country of origin for this product is the United States. To see the full specifications for this product, please see our product manual found under the documentation tab if available.

Note: The UX120-018 logger is intended for use on 15 AMP circuits (NEMA 5-15P) with a working voltage of 120V AC ±10% at 50/60Hz and a max power of 1800W.

  • Indoor use only

  • Insulation category 2

MetInfo enterprise content manager system | MetInfo CMS

RMS Voltage Accuracy:0.5% up to 14 Amp continuous; up to 1.0% over 14 Amp when equipment being monitored is at 100% duty cycle
RMS Current Accuracy:0.5% up to 14 Amp continuous; up to 1.0% over 14 Amp when equipment being monitored is at 100% duty cycle
Active Power Accuracy:0.5% up to 14 Amp continuous; up to 1.0% over 14 Amp when equipment being monitored is at 100% duty cycle
Active Energy Accuracy:0.5% up to 14 Amp continuous; up to 1.0% over 14 Amp when equipment being monitored is at 100% duty cycle
Power Factor Accuracy:±0.02
Drift:Up to 0.5% typical within 1 year
Resolution:Volts, rms10mVAmps, rms0.1mAActive Power10mW down to 1 watt loads @ 120VACApparent Power10mVAPower Factor0.01 PF
Operating Environment:Logging: 5° to 40°C (41° to 104°F); 0 to 95% RH (non-condensing), up to 2,000 m (6,562 ft) altitude
Operating Modes:Meter or logging when launched with HOBOware
Logging Rate:1 second to 18 hours, 12 minutes, 15 seconds
Statistics Sampling Rate:60 Hz or 16.67 mS single-cycle
Memory Modes:Wrap when full or stop when full
Start Modes:Immediate, push button, date & time, or next interval
Stop Modes:When memory full, push button, or date & time
Restart Mode:Push button
Time Accuracy:±1 minute per month at 25°C (77°F), see Plot A
Power Source:Line-powered with 0.92 m (3 ft) AC power cord or two AAA 1.5 V alkaline batteries, user replaceable
Battery Life:2 years with line power; 6 months battery only (no line power) with logging rate of 1 minute or greater operating at 25°C (77°F)
Memory:4 MB (1.4 million measurements, maximum)
Download Type:USB 2.0 interface
Full Memory Download Time:Approximately 1.5 minutes
LCD:LCD is visible from 0° to 50°C (32° to 122°F); the LCD may react slowly or go blank in temperatures outside this range
Size:13.97 x 7.62 x 4.75 cm (5.5 x 3 x 1.87 in.)
Weight:230.8 g (8.14 oz)
Ratings:IP50;
UL LogoUL Listed; UL Listed to Canadian safety standards
Calibration:This device has been calibrated using equipment that has been tested in accordance with ANSI C12.20 0.5%.

Time Accuracy